Skip to content

Language

AEMC 2138.10 Multi-Function Installation Tester Model C.A 6116N Kit (US)

SKU 2138.10

Model Number: AEM213810

Original price $3,268.00 - Original price $3,268.00
Original price
$3,268.00
$3,268.00 - $3,268.00
Current price $3,268.00

SPECIAL ORDER ONLY - Extended Lead Times
Includes C177A, DataView® Software

The C.A 6116N is a multi-function instrument for testing electrical installations for compliance with national and international standards (IEC 60364-6, NF C 15-100, VDE 100, FD C 16-600, and others). It features advanced design, ergonomics, simplicity, performance, speed, and accuracy. Suitable for all neutral systems (TT, TN, IT), the instrument is ideal for all sectors including industrial, residential, and others. It measures continuity, resistance, insulation, earth and selective earth, loop impedances, type A and AC RCDs, as well as voltage, frequency, current (via a clamp), active power, harmonics, and phase rotation. The instrument can store up to 1,000 tests, which can be downloaded and processed with the included DataView® data analysis software.

CONTINUITY / RESISTANCE
I Rated  •  Range  • Resolution I > 200 mA  •  39.99 Ω  •  0.01Ω   ± (1.5 % of R + 2 cts)
12 mA  • (39.99 and 399.9) Ω  •  (0.01 and 0.1) Ω  •± (1.5 % of R + 5 cts) with beep
Range • Resolution •  Accuracy 4 kΩ •  1 Ω  •  ±(1.5 % of R + 5 cts)
(40 to 400) kΩ  •  (10 - 100) Ω  •  ±(1.5 % of R + 2 cts)
INSULATION         
Rated Voltage U test: (50, 100, 250, 500, and 1000) VDC
Range • Resolution • Accuracy 0.01 MΩ to 2 GΩ   •  0 kΩ to 1 MΩ  • ± (5 % of R + 3 cts)
Short Circuit Current ≤ 3 mA
3P GROUND
Range •  Resolution •  Accuracy (0.50 to 40) Ω  •  0.01 Ω  •  ± (2 % of R + 10 cts)
(40 Ω to 15 kΩ)  • (0.1 to 1) Ω • ± (2 % of R + 2 cts )
(15 to 40) kΩ  •  10 Ω  •  ± (10 % of R + 2 cts )
Others Measurement of resistance of auxiliary stakes RH & RS (up to 40 kΩ)
Ufk Complies with SEV 3569
1P SELECTIVE GROUND
Range
Resolution
Accuracy
(0.20 to 39.99) Ω
(40 to 399.9) Ω 
(0.01 – 0.1) Ω  ± (10 % of R + 10 cts) (ISel via clamp)
LOOP IMPEDANCE (Zs (L-PE0 AND Zi (L-N OR L-L) – 1P LIVE GROUND
Live Ground
Installation Voltage 
Frequecy
(90 to 500) V 
(15.8 to 17.5) Hz 
(45 to 65) Hz
High-current mode with TRIP
Zs (L- PE) & Zi (L- N or L - L)
Range •  Resolution •  Accuracy
Max. test current: 7.5 A  
(0.100 to 0.5) Ω • 0.001 Ω  •  ± (10 % of R + 20 cts) 
(0.5 to 3.999)  Ω • 0.001 Ω •  ± (5 % of R + 20 cts)
(3.999 to 39.99) Ω • 0.01 Ω  •  ±(5 % of R + 2 cts)
(39.99 to 399.99) Ω • 0.1 Ω •  ± (5 % of R + 2 cts)
NO TRIP mode (Zs (L – PE) Only)
Range •  Resolution •  Accuracy
Test current (6, 9,and 12) mA (as required)
(0.20 to 0.99) Ω •  0.01 Ω •  ± (15 % of R + 10 cts)
(1.00 to 1.99) Ω •  0.01 Ω •  ± (15 % of R + 3 cts)
(2.00 to 39.99)  Ω •  0.01 Ω •  ± (10 % of R + 3 cts)
(40.00 to 399.9) Ω •  0.1Ω •  ± (5 % of R + 2 cts)
(400 to 3999) Ω •  1 Ω •  ± (5 % of R + 2c ts)
Calculation of IK short circuit current (PFC (Zs), I Sc PSCC (Zi) Fault current and short-circuit current: (0.1 to 20) kA
Others Measurement of the resistive and inductive components of Zs and Zi impedances
AC and type RCDs
Installation Voltage
Frequency
(90 to 500 ) V 
(15.8 to 17.5) Hz and (45 to 65) Hz
IΔn 10/30/100/500/650/1000 (90 to  280) V or variable  ramp and pulse test
N-Trip Test At ½ IΔn – Duration 1000 ms or 2000 ms
Ramp Mode 0.2 to 0.5 x IΔn(Uf) / 0.3 x IΔn to 1.06 IΔn increments of 3.3% x IΔn
Trip test:  R:
Range / Resolution / Accuracy
0.2 to 0.5 x IΔn(Uf) / 0.5 x IΔn / 2 x IΔn(selective) /  5 x IΔn
Pulse: 0 to 500ms/0.1 and 1ms / 2ms, Ramp mode: 0 to 200ms / 0.1ms / 2 ms
OTHER MEASUREMENTS
Current by Current Probe C177A 5.0 mA t0 199.9 A
Current by Current Probe MN77 (1 mA*) 5.0 mA to 19.99 A
Voltage 0 to 550 VAC/DC / DC and (158 to 500) Hz
Frequency (10 to 500) Hz
Phase Rotation (20 to 500) VAC
Active Power (0 to 110) kW single phase – (0 to 330) kW three-phase
Simultaneous display of voltage and current waveforms
Harmonics Voltage and Current  up to 50th order  THD-F / THD-R
GENERAL SPECIFICATIONS
Display Large 5.7 inch backlit graphic color LCD 320 x 240 pixels
Storage/Communication USB for data transfer to DataView® software (included)
Power Supply Rechargeable Lithium-Ion 10.8 V, 5.8 A • h
Battery Life Up to 30 hours
Protection IP 53 / IK04
Dimensions
Weight
(11 x 7.48 x 5.04) in (280 x 190 x 128) mm
4.85 lbs (2.2 kg)
EMC IEC61326-1
Electrical Safety IEC61010-1 – 600 V CAT III 300 V CAT IV – IEC 61557 